OAR 837-047-0130
Installation and Location of Carbon Monoxide Alarms and Detectors


(1)

All carbon monoxide alarms or detectors must be installed in accordance with the manufacturer’s recommended instructions and located in accordance with these rules and applicable building code at the time of construction or alteration of the dwelling.

(2)

One and Two Family Dwellings and Manufactured Dwellings: A properly functioning carbon monoxide alarm must be located within each bedroom or within 15 feet outside of each bedroom door. Bedrooms on separate floors in a structure containing two or more stories require separate carbon monoxide alarms.

(3)

Multi Family Housing:

(a)

A properly functioning carbon monoxide alarm must be located within each bedroom or within 15 feet outside of each bedroom door in dwelling units containing a carbon monoxide source or are connected to a common area containing a carbon monoxide source. Bedrooms on separate floors in a structure containing two or more stories require separate carbon monoxide alarms.

(b)

A carbon monoxide alarm must be installed in any enclosed common area within the building if the common area is connected by a door, ductwork, or ventilation shaft to a carbon monoxide source located within or attached to the structure.

Source: Rule 837-047-0130 — Installation and Location of Carbon Monoxide Alarms and Detectors, https://secure.­sos.­state.­or.­us/oard/view.­action?ruleNumber=837-047-0130.