OAR 918-271-0050
Inspection of Secondary Considerations


(1)

Electrical installations not specified by OAR 918-271-0040 (Mandatory Inspection Practices) are secondary items.

(2)

At least 30 percent of all secondary items at a job site shall be inspected using a sampling process that reviews all separate categories of secondary items. If code violations are found within the samples inspected, an additional ten percent of the secondary items shall be inspected.

(3)

If additional violations are found, the inspector shall:

(a)

Require the permit holder to check all other similar categories of installations on the job site;

(b)

Advise of the correction of all defects; and

(c)

If warranted, inspect all other similar categories of installations on the job site.