OAR 333-029-0095
Fire Safety


(1)

Portable fire extinguishers shall be provided in travelers’ accommodations and hostels. Such fire extinguishers shall:

(a)

Have a minimum rating of 2A:10B:C;

(b)

Be located so as to require no more than 75 feet of travel distance to an extinguisher.

(2)

Equivalent protection as outlined by NFPA No. 10 shall be accepted.

(3)

Every gas water heater, and every other gas fired appliance except gas plates and gas ranges, installed or serviced for use in any rental units, shall be effectively vented as required by the State Fire Marshal.

(4)

Liquefied petroleum gas storage tanks shall conform in construction, design, installation, and operation with the rules of the State Fire Marshal.
[Publications: Publications referenced are available from the agency.]
Last Updated

Jun. 8, 2021

Rule 333-029-0095’s source at or​.us