OAR 345-024-0090
Siting Standards for Transmission Lines


To issue a site certificate for a facility that includes any transmission line under Council jurisdiction, the Council must find that the applicant:

(1)

Can design, construct and operate the proposed transmission line so that alternating current electric fields do not exceed 9 kV per meter at one meter above the ground surface in areas accessible to the public;

(2)

Can design, construct and operate the proposed transmission line so that induced currents resulting from the transmission line and related or supporting facilities will be as low as reasonably achievable.